| Description | Value |
| Input | Rated input voltage | 6kV/10kV, -15%~+10% |
| Input frequency | 50/60Hz, ±5% |
| Input power factor | ≧0.97(Full load) |
| System efficiency | ≧98%(Full load) |
| Input current harmonic | ≦2%, meet IEC standards of IEEE519~1992 and GB/T14519~93 Quality of electric energy supply-Harmonics in public supply network. 36pulse. |
| Output | Output voltage | 0~6kV/10kV |
| Output frequency | 0~120 Hz |
| Output current harmonic | ≦2% |
| Control performance | Control mode | Vector control without PG, V/F control ;Vector control with PG |
| Control system | DSP, FPGA, ARM |
| Power system | UPS, Sustainable 30mins while Power off |
| HMI | 10 inch touch screen |
| Speed ratio | 1:50 (VF), 1:100 (SVC),1:200(VC) |
| Speed control precision | ±1% the maximum speed (VF), ±0.4% the maximum speed (open loop vector);±0.2% the maximum speed (VC) |
| Torque response time | <200ms(open loop vector);<100ms(VC) |
| Starting torque | 150% of the rated torque |
| Overload protection | 120% of the rated current: 2 mins |
| 150% of the rated current: 5 s |
| 200% of the rated current: protect immediately |
| ACC/DEC time | 0-3600s, customized |
| Signal I/O | Digital input | 8channels digital input |
| Digital output | 8 channels relay output |
| Analog input | 3 channels: AI1, AI2: 0~10V/4~20mA; AI3: -10V~10V |
| Analog output | 4 channels: AO1, AO2,AO3, AO4: 0~10V/4~20mA |
| High speed pulse input | 1 channel: Input range 0~50kHz |
| High speed pulse output | 1 channel: Output range 0~50kHz |
| Communication method | Modbus, RS485 interface,Optional: Profibus-DP, Ethernet |
| Protection function | System | Overcurrent, overvoltage, undervoltage, motor overload, inverter overload, input phase loss, output phase loss |
| Overheating, temperature controller fault, communication fault, access fault, uplink communication fault, downlink communication fault, fan overheating |
| Unit | Optical fiber uplink communication fault, optical fiber downlink communication fault, overvoltage, undervoltage, power supply overheating, input phase loss, VCE fault, bypass failure |
| Others | Installation method | Cabinet mounting |
| Protection degree | IP30 |
| Noise degree | ≤75dB |
| Feed in and out method | Bottom in and out; other methods are optional |
| Cooling | Forced-air cooling |
| Control power supply | AC 380V±10% |
| MTBF | 50000h |
| Temperature of running environment | -5℃~+50℃ |
| Altitude | Below 1000m; derate 1% for every additional 100m if the sea level is above 1000m. |
| Storage | Keep away from dust, direct sunlight, flammable or corrosive gas, oil, steam and vibration. |
| Vibration | 2~9Hz displacement 3mm; 9~20Hz ACC 9.8m/s2; 20~55Hz ACC 2m/s2; 55~200Hz ACC 1m/s2 |